Fault 1: Diesel generator set has low speed or unstable speed

Cause
1 Fuel filter blocked
2 The fuel system is not working properly
3 The governor is not working properly.
4 Low ambient temperature or no warm-up
5 engine speed is too low

Solution
1 Replace the fuel filter
2 Check the engine governor
3 Check the engine's preheating system, run the engine at no load and reach the operating temperature

Fault 2: The diesel generator set tries to start but cannot succeed

Cause

1 Battery power is insufficient
2 Battery connector corrosion or loose cable connection
3 Insufficient fuel in the engine cylinder
4 There is air in the fuel oil circuit
5 fuel filter blocked
6 The fuel system is not working properly
7 air filter blocked
8 Ambient temperature is too low
9 governor is not working properly
10 control panel startup circuit failure

Solution
1 Check and charge the battery, replace the battery if necessary
2 Check the binding posts of the connecting cable, tighten the nuts, and replace the corroded connecting terminals and nuts.
3 Check the fuel tank and fill it with oil
4 Exhaust the air from the fuel system
5 Replace the fuel filter
6 Replace the air filter
7 Check oil viscosity and grade
8 Check the control panel start/stop control circuit

Fault 3: The voltage frequency is low or the indication is zero

Cause
1 Fuel filter blocked
2 The fuel system is not working properly
3 The governor is not working properly.
4 engine speed is too low
5 indicating instrument failure
6 Instrument connection failure

Solution
1 Replace the oil filter
2 Check the engine governor
3 Check the instrument and replace the meter if necessary
4 Check the instrument connection circuit
5 Check engine governor

Fault 4: Diesel generator set has low oil pressure

Cause
1 oil level is high
2 lack of oil
3 oil filter blocked
4 oil pump workload is not normal
5 sensor, control panel or wiring failure

Solution
1 Release excess oil
2 Add oil to the oil sump and check for leaks
3 Change the oil filter
4 Check if the sensor and control panel and grounding cable are loose or disconnected, and check if the sensor needs to be replaced.

Fault 5: Diesel generator set can not start

Cause
1 circuit is not working properly
2 battery power is insufficient
3 Battery connector corrosion or loose cable connection
4 Poor cable connection, charger or battery failure
5 Start motor failure
6 control panel startup circuit failure

Solution
1 Check electrical reasons
2 Check and charge the battery, replace the battery if necessary
3 Check the control panel start/stop control circuit
4 Check the connection between the charger and the battery
5 Check the binding posts of the connecting cable, tighten the nuts, and replace the corroded connecting terminals and nuts.

XIAMEN AOT ELECTRONIC TECHNOLOGY CO.,LTD which has 15 years experience in diesel generator spare parts manufacturing. We provide full kinds of generator spare parts for engine replacement and other related electric products such as automatic transfer switch, electric Relay etc. Welcome to contact us for more information.

Contact: Ms.Lika (Sales)
Email: sales@aotchina.com
Phone: 0086 182 5072 9722
Skype: sales@aotchina.com
Web: www.aotchina.com

CONTACT US

Contact: Jack

Phone: 0086-19906045242

Tel: 0086-592-7161550

Email: sales@aotchina.com

Add: No.21 Yufu Road, Jimei Disctrict, Xiamen City, China 361000

Scan the qr codeClose
the qr code