TECHNICAL DATA:
Voltage Set-up:The voltage set up when the remnant magnetism greater than 4V 25Hz
Input power Supply:AC 160~260V 50/60Hz
Maximum Output: DC 5A 95V(when the voltage reaches AC 240V)
Frequency Compensation:Built-in low speed protective circuit.
INPUT:
Voltage Jumper selectable
95-132V ac or 190-264 Hz nominal
Frequency 50-60 Hz nominal
OUTPUT:
Voltage max 90V dc at 207V ac input
Current continuous 2A dc
Intermittent 5A for 10 secs
Resistance 20 ohms minimum
REGULATION: +/-1%
This is one kinds of currency AVRs for brushless generators in the world.
TECHNICAL DATA:
INPUT:
Voltage :160-260V AC
Frequency :50-60 Hz nominal
Brushless Generator AVR GAVR-12A |
||
Input |
Sensing voltage |
180~260VAC,1 phase 2 wire |
Power voltage |
180~260VAC,1 phase 2 wire |
|
Output |
Voltage |
Max. 90VDC@240VAC input |
Current |
Continuous 4A |
|
Current |
Intermittent 7A for 10SEE |
|
Resistance |
Min.12Ω Max.100Ω |
|
Voltage Build-up |
Residualvolts at AVR teminal>5VAC |
|
External Volts Adjustment |
±7% with 1KΩ 1 with trimmer |
|
Soft start ramp time |
2sec. |
|
Unit power dissipation |
Max.8 Watt |
|
EMI suppression |
Internal electromagnetic interference filtering |
|
Thermal. Drift |
0.03% per°C chage in AVR ambient |
|
Under freqency protection |
60Hz system presets knee point at 55Hz |
|
(Factory setting) |
50Hz system presets knee point at 45Hz |
|
Volts regulation |
<±1%(with 4% engine governing) |
|
Environment |
Vibration 3G@100~2K Hz |
|
Operating temperature -40~60°C |
||
Relative humidity<95% |
||
Storage temperature -40~85°C |
||
Dimensions |
12.1*9.2*6cm |
Contact: Jack
Phone: 0086-19906045242
Tel: 0086-592-7161550
Email: sales@aotchina.com