  • Product description: HGM6100K series generator controller integrating digital, intelligent and network techniques is used for automatic control system of diesel generator. It can carry out functions including automatic st
  • INQUIRY

Generator Control Panel Smargent Controller HGM6120K

HGM6100K series Generator Controller integrating digital, intelligent and network techniques is used for automatic control system of diesel generator. It can carry out functions including automatic start/stop, data measure and alarming. The controller uses LCD display, optional Chinese and English display interface with operation easy and reliable. HGM6100K series generator controller uses micro-processing technique which can carry out precision measure, constant value adjustment, timing and threshold setting and etc. of multi-parameters. It can be widely used in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability.

 

PERFORMANCE AND CHARACTERISTICS

HGM6100K controller has four types:

HGM6110K/6110KC: Automatic Start Module, it controls generator to start/stop by remote start signal;

HGM6120K/6120KC: Based on HGM6110K/6110KC and add mains AC monitoring, Mains/Generator automatic switching control functions (AMF), especially suitable for the automation system composed by Mains and Generator.

 

Note1: HGM6110KC/6120KC with RS485 interface, HGM6110K/6120K without RS485 interface. Note2: And then take HGM6110KC/6120KC with text as an example to describe.

 

Operating Voltage

DC8. 0V to 35. 0V, Continuous Power Supply

Power Consumption

<3W

Alternator Input Range

3-Phase 4 Wire

2-Phase 3 Wire

Single phase 2 wire

 

15V AC - 360 V AC (ph-N)

15V AC - 360 V AC (ph-N)

15V AC - 360 V AC (ph-N)

Alternator Input Frequency

50Hz - 60 Hz at rated engine speed

Magnetic Input Range

+/- 0. 5 V to 70 V Peak

Magnetic Input Frequency

10,000 Hz (max) at rated engine speed.

Start Relay Output

7 Amp DC at supply voltage.

Fuel Relay Output

7 Amp DC at supply voltage.

Auxiliary Relay Output (1-4)

(1)7 Amp DC at supply voltage,(2)7A 250VAC free voltage contact,(3,4)16A 250VAC free voltage contact.

Dimensions

200mm x 144mm x 50mm

Panel cutout

184mm x 139mm

Operating Temperature Range

-25 to +70°C

Storage Condition

Temperature: (-30 - 80)°C

C. T. Burden

2. 5VA

C. T. Secondary

5A

Weight

0. 55kg