Automatic Voltage Regulator (AVR)

  • Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11
  • Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11
  • Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11
  • Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11
Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11

Generator AC Voltage Regulation Stabilizer AVR DECS-100-B11

  • Model: AVR DECS100-B11
  • Origin: China
  • Warranty: 1 Year
  • In stock: Yes
  • Product description: The DECS-100 is a microprocessor-based regulation system designed to control the output of a brush-less excited synchronous generator. The DECS-100 is perfect for paralleling applications where genera
  • INQUIRY

Automatic Voltage Regulator BASLER AVR DECS100-B11


FEATURES

• Microprocessor based

• 0.25% Voltage Regulation Accuracy

• 0.5% accuracy up to 40% THD (harmonics associated with 6 SCR load)

• 63Vdc @ 7Adc PWM output

• 0-3X V/Hz limiting

• Soft Start capability

• 20 standard stability selections and one customized selection

• VAR/PF control

• Over excitation limiting

• Under excitation limiting

• Voltage Matching

• Manual Mode (Field current regulation)

• Paralleling input from 1 or 5A CT secondaries

• Nominal sensing inputs of 120, 240, 480 and 600Vac

• Power Input from 50/60Hz shunt connections or PMGs operating at 50 to 400Hz

• Five generator protection functions including Loss of Sensing transfer to manual

• Alarm Contact Output

• Accessory input

• LED Annunciation of operating conditions

• Setup via PC using BESTCOMS software (included)

• cURus recognition per UL 508 and CSA Standard C22.2 No. 14

• DNV Standard for Certification 2.4

• CE compliant

 

SPECIFICATIONS

Power Input

Voltage

88-250Vac

Phase

Single- or three-phase

Burden

650VA

Frequency

50 to 400Hz

Minimum Build-up Voltage

6.0Vac

Sensing Input

Nominal Voltage Input

100/120, 200/240, 400/480, 600Vac, Single- or three-phase

Burden

<1VA

Current Input

1 or 5 Amp (two models)

Frequency

Frequency

Accessory Input

±1Vdc creates a ±10% adjustment (respectively) for AVR, FCR and VAR set point

±1Vdc creates a ±0.1PF adjustment (respectively) in the PF mode set point. (adjusts only the active regulation mode)

DC Output

Continuous voltage

63Vdc

Continuous current

7.0Adc

10 second Forcing Voltage

135Vdc (with nominal input applied)

10 second Forcing Current

15.0Adc

Minimum Field Resistance

9 Ohms

Alarm Contact Output

Dry Contact Rated

120/240Vac - make 30A for 0.2S, carry 7A continuously,

break 0.1A inductive

 

REGULATION ACCURACY

Regulation accuracy

±0.25% no load to full load

Temperature drift

±0.5% for a 40°C change in one hour

Response time

<1 cycle to the limit of the A/D converter

THD

±0.25% for 20% THD and ±0.5% for 40% THD


The product is not original but can be compatible with the original one.

Scan the qr codeClose