General description:
Positive voltage build up from residual levels is ensured by the use of efficient semiconductors in the power circuitry of the AVR.
The AVR is linked with the main stator windings and the exciter field windings to provide closed loop control of the output voltage with load regulation of +/- 1.0%.
In addition to being powered from the main stator, the AVR also derives a sample voltage from the output windings for voltage control purposes. In response to this sample voltage, the AVR controls the power fed to the exciter field, and hence the main field, to maintain the machine output voltage within the specified limits, compensating for load, speed, temperature and power factor of the generator.
A frequency measuring circuit continually monitors the generator output and provides output under-speed protection of the excitation system, by reducing the output
voltage proportionally with speed below a pre-settable threshold. A manual adjustment is provided for factory setting of the under frequency roll off point, (UFRO). This can easily be changed to 50 or 60 Hz in the field by pushon link selection.
Provision is made for the connection of a remote voltage trimmer, allowing the user fine control of the generator's output.
An analogue input is provided allowing connection to a Newage Power Factor controller or other external devices with compatible output.
The AVR has the facility for droop CT connection, to allow parallel running with other similarly equipped generators.
Technical specification (Full Specification file download click here)
Input |
Voltage |
190-264V ac |
Frequency |
50-60 Hz nominal |
|
Phase |
1 |
|
Wire |
2 |
|
Output |
Voltage |
max 90V dc at 207V ac input |
Current |
continuous 4A dc, intermittent 6A for 10 secs |
|
Resistance |
15 ohms minimum |
|
Regulation |
+/- 1.0% |
|
Thermal Drift |
0.04% per deg. C change in AVR ambient |
|
Typical system response |
AVR response |
20ms |
Filed current to 90% |
80 ms |
|
Machine Volts to 97% |
300ms |
|
External voltage adjustment |
+/-10% with 1 k ohm 1 watt trimmer |
|
Under frequency protection |
Set point |
95% Hz |
Slope |
170% down to 30 Hz |
|
Unit power dissipation |
12 watts maximum |
|
Build up voltage |
4 Volts @ AVR terminals |
|
Analogue Input |
Maximum input |
±5V dc |
Sensitivity |
1v for 5% |
|
Input resistance |
1k ohm |
|
Quadrature Droop Input |
10 ohms burden |
|
Max. sensitivity: 0.07 A for 5% droop 0PF |
||
Max. input: 0.33A |
||
Environmental |
Vibration |
20-100 Hz,50mm/se |
100Hz - 2kHz, 3.3g |
||
Operating temperature |
-40 to +70 Deg. C |
|
Relative Humidity 0-70 Deg. C |
95% |
|
Storage temperature |
-55 to +80 Deg. C |
NOTES
1. With 4% engine governing.
2. After 10 minutes.
3. Applies to Mod status S onwards. Generator de-rate
may apply. Check with factory.
4. Factory set, semi-sealed, jumper selectable.
5. Any device connected to the analogue input must be
fully floating (galvanically isolated from ground), with an
insulation strength of 500V ac.
6. Non condensing.