Automatic Voltage Regulator (AVR)

  • Generator Automatic Voltage Stabilizer AVR R250
  • Generator Automatic Voltage Stabilizer AVR R250
  • Generator Automatic Voltage Stabilizer AVR R250
  • Generator Automatic Voltage Stabilizer AVR R250
  • Generator Automatic Voltage Stabilizer AVR R250
Generator Automatic Voltage Stabilizer AVR R250Generator Automatic Voltage Stabilizer AVR R250Generator Automatic Voltage Stabilizer AVR R250Generator Automatic Voltage Stabilizer AVR R250Generator Automatic Voltage Stabilizer AVR R250

Generator Automatic Voltage Stabilizer AVR R250

  • Model Number: R250
  • Brand Name: AOT
  • Warranty: 1 year
  • In stock: yes
  • Product description: Automatic Voltage Regulator AVR R250 for Generator, Leroy somer R250 AVR controls the excitation current according to the alternator's output voltage. With a very simple conception, the shunt excita
  • INQUIRY

Generator Automatic Voltage Regulator AC Stabilizer AVR R250


Leroy somer R250 AVR controls the excitation current according to the alternator's output voltage.

With a very simple conception, the shunt excitation alternator is auto excited with a R250 and

excitation alternator does not have a short circuit capacity, voltage regulation: around ±0.5%.


1.Leroy Somer Automatic Voltage Regulator R250
2. Suits leroy somer brushless alternator
3.Analogic Automatic Voltage Regulator with transistor

4.Applications Alternators LSA 42.2, 43.2, 44.2, 46.2, 47.2. Compatible with the SHUNT excitation syste. 

The R250 is in Compliance with: IEC, VDE, NEMA, BS, CSA, UL508 CE low voltage.


Voltage regulation

Around ± 0.5 %

Supply range

85 to 139 V

Potentiometer for voltage setting

1000Ω /0.5W min. setting range ±5%

Operating at 50 Hz

Threshold at 48 Hz without LAM forimpactsbetween 30 and 40% of the rated
Load

Threshold at 48 Hz with LAM 13% forimpacts between 40 and 70% of the rated
Load.

Threshold at 48 Hz with LAM 25% for impacts > 70% of the rated load

Operating at 60 Hz

Threshold at 58 Hz without LAM forimpacts between 30 and 40% of the
Rated load

Threshold at 58Hz with LAM 13% for impacts 40 and 70% of the rated load

Threshold at 58Hz with LAM 25% for impacts > 70% of the rated load

Specific operating

Threshold at 57Hz without LAM for speed variations at a steady state > 2 Hz

Threshold at 65Hz without LAM for speed and tractelec / gearlec (U/F gradient)

Special: the factory setting 48Hz 2U/F gradient; a special programme is
Possible on request.

Threshold at 47.5 Hz without LAM for speed variations at a steady state > 2 Hz

Scan the qr codeClose